Rated switching distance 5 mm
Mounting conditions Flush
Secured operating distance ≤ (0.81 × Sn) mm
Correction factors St37 = 1; Al = 0.3; stainless steel = 0.7;
Ms = 0.4
Repeat accuracy ≤ 2 % of full scale
Temperature drift ≤ ±10 %
Hysteresis 1…10 %
Electrical data
Output function 2-wire, NAMUR
Switching frequency 1 kHz
Voltage Nom. 8.2 VDC
Non-actuated current consumption ≥ 2.1 mA
Actuated current consumption ≤ 1.2 mA
Approval acc. to KEMA 02 ATEX 1090X
Internal capacitance (Ci)/inductance (Li) 150 nF/150 µH
Device marking EX II 1 G Ex ia IIC T6 Ga/II 1 D Ex ia IIIC
T135 °C Da
(max. Ui = 20 V, Ii = 20 mA, Pi = 200 mW)
Mechanical data
Design Threaded barrel, M18 x 1
Dimensions 34 mm
Housing material Metal, CuZn, Chrome-plated
Active area material Plastic, PA12-GF30