Application
Design housing for DIN rail mounting
Application field installation
Electrical data
Operating voltage[V] 26.5...31.6 DC; ("supply class 2" to cULus)
Max. current consumption from AS-i[mA] 150
Max. current load total[A] 4
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital inputs: 2; Number of digital outputs: 2
Inputs
Number of digital inputs 2
Input circuit of digital inputs PNP
Sensor supply of the inputs AS-i
Power supply[V] 18...30; (via flat cable)
Max. total current rating of inputs[mA] 100
Input current High[mA] 6...10
Input current Low[mA] 0...2
Switching level high[V] > 11
Digital inputs protected against short circuits yes
Outputs
Number of digital outputs 2
Circuit PNP
Voltage range DC[V] 15...30; (to PELV; via flat cable)
Max. current load per output[mA] 2000; (utilisation category DC-13 (control of electromagnets): 40 W (IEC 60947-5-1))
Short-circuit proof yes
Electrically separated yes
Actuator supply outputs AUX
Operating conditions
Ambient temperature[°C] -25...70
Protection IP 67
Tests / approvals
EMC
EN 50295
IEC 61000-6-2
MTTF[years] 188
AS-i classification
AS-i version 2.11; 3.0
AS-i addressing addressing socket
Extended addressing mode no
AS-i master profile M2; M3; M4
AS-i profile S-3.0.E
AS-i I/O configuration[hex] 3
AS-i ID code[hex] 0.E
Assignment of the data bits
data bit D0 D1 D2 D3
input 1 2 - -
socket I-1 I-2 - -
pin 2+4 2+4 - -
Output - - 3 4
socket - - O-3/4 O-3/4 O-4
pin - - 4 2 4
Mechanical data
Weight[g] 195.5
Housing rectangular
Type of mounting AS-i flat cables directly connectable; mounting on DIN rail; (TH35 (EN 60715))
Dimensions[mm] 103 x 45 x 44.7
Materials PA; piercing contacts: CuSn6 nickel-plated and tin-plated
Displays / operating elements
Display
operation LED, green
errors LED, red
function LED, yellow
Electrical connection
Module connection Flat cables
Accessories
Items supplied
lower part
Accessories (optional)
Protective cap: M12, E73004
Remarks
Remarks
Inputs and outputs must be electrically isolated.
Do not connect any of the following points to an external potential:
I-, I+, I1, I2
The connections are electrically connected with the AS-i cable.
Pack quantity 1 pcs.
Electrical connection
quick mounting technology for AS-i flat cable: ; three orientations possible
Electrical connection - Inputs
Connector: M12; coding: A
Electrical connection - Outputs
Connection Connector: M12