Electrical data

Operating voltage[V] 26.5...31.6 DC; ("supply class 2" to cULus)

Max. current consumption from AS-i[mA] 150

Max. current load total[A] 4

Integrated watchdog yes

Inputs / outputs

Number of inputs and outputs Number of digital inputs: 2; Number of digital outputs: 2

Inputs

Number of digital inputs 2

Input circuit of digital inputs PNP

Sensor supply of the inputs AS-i

Power supply[V] 18...30; (via flat cable)

Max. total current rating of inputs[mA] 100

Input current High[mA] 6...10

Input current Low[mA] 0...2

Switching level high[V] > 11

Digital inputs protected against short circuits yes

Outputs

Number of digital outputs 2

Circuit PNP

Voltage range DC[V] 15...30; (to PELV; via flat cable)

Max. current load per output[mA] 2000; (utilisation category DC-13 (control of electromagnets): 40 W (IEC 60947-5-1))

Short-circuit proof yes

Electrically separated yes

Actuator supply outputs AUX

Operating conditions

Ambient temperature[°C] -25...70

Protection IP 67

Tests / approvals

EMC

EN 50295

IEC 61000-6-2

MTTF[years] 188

AS-i classification

AS-i version 2.11; 3.0

AS-i addressing addressing socket

Extended addressing mode no

AS-i master profile M2; M3; M4

AS-i profile S-3.0.E

AS-i I/O configuration[hex] 3

AS-i ID code[hex] 0.E

Assignment of the data bits

data bit D0 D1 D2 D3

input 1 2 - -

socket I-1 I-2 - -

pin 2+4 2+4 - -

Output - - 3 4

socket - - O-3/4 O-3/4 O-4

pin - - 4 2 4

Mechanical data

Weight[g] 195.5

Housing rectangular

Type of mounting AS-i flat cables directly connectable; mounting on DIN rail; (TH35 (EN 60715))

Dimensions[mm] 103 x 45 x 44.7

Materials PA; piercing contacts: CuSn6 nickel-plated and tin-plated

Displays / operating elements

Display

operation LED, green

errors LED, red

function LED, yellow

Electrical connection

Module connection Flat cables

Accessories

Items supplied

lower part

Accessories (optional)

Protective cap: M12, E73004

Remarks

Remarks

Inputs and outputs must be electrically isolated.

Do not connect any of the following points to an external potential:

I-, I+, I1, I2

The connections are electrically connected with the AS-i cable.

Pack quantity 1 pcs.

Electrical connection

quick mounting technology for AS-i flat cable: ; three orientations possible

Electrical connection - Inputs

Connector: M12; coding: A

Electrical connection - Outputs

Connection Connector: M12