General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 11+, 12-
Rated voltage 19 ... 30 V DC
Ripple within the supply tolerance
Power dissipation ≤ 1.2 W
Power consumption ≤ 1.6 W
Input
Connection side field side
Connection terminals 4 (common), 1, 3 and 5 (supply -), 2 and 6 (signal -)
Input resistance 10 kΩ terminals 4 (common), 6-/2-
Output current terminals 4 (common), 5-: > 10 mA at -21 V or > 20 mA at -18 V
terminals 4 (common), 1-: 5.3 mA ±0.4 mA at -10 V
terminals 4 (common), 3-: 3.6 mA ±0.7 mA at -10 V, 20 °C (68 °F)
Transmission range -20 ... 0 V
Output
Connection side control side
Connection terminals 7-, 8+
Voltage -20 ... 0 V
Load ≥ 9 kΩ (3-wire sensor), ≥ 2 kΩ (2-wire sensor)
Output resistance 24 Ω typ., 27 Ω maximum
Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer.
Transfer characteristics
Cut-off frequency 10 kHz (-0,1 dB)
20 kHz (-1 dB)
Deviation DC transfer error (with 10 kΩ load) < 10mV
After calibration additional error with AC superimposed is ±5 mV at 20 °C (68 °F) at any point within the span, provided that the alternating component of the input voltage is not excessive, e. g.
- square waves (0 ... 20 kHz): 5 Vpp
- sine waves (0 ... 20 kHz): the full span of 20 Vpp (= 100 g peak acceleration at 100 mV/g) is acceptable.
Influence of ambient temperature (< 100 ppm of span)/K at any point within the span
Time delay relative to input 7.1 ±0.3 µs
Ripple in 200 kHz bandwidth < 20 mVrms
in 20 kHz bandwidth < 3 mVrms
Galvanic isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elements LED
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2017
EN IEC 61326-3-2:2018
Degree of protection IEC 60529
Protection against electrical shock UL 61010-1
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 125 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height 119 mm
Width 20 mm
Depth 115 mm
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001