Supply
Connection SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage 19 ... 30 V DC bus powered via Termination Board
Ripple ≤ 10 %
Rated current ≤ 30 mA
Power dissipation ≤ 500 mW
Power consumption ≤ 500 mW
Input
Connection side field side
Connection SL2: 5a(+), 5b(-)
Rated values acc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.7 mA
Pulse/Pause ratio min. 20 ms / min. 20 ms
Output
Connection side control side
Connection SL1: 8a, 7a; 10a, 9a
Output I signal ; relay
Output II signal or fault message ; relay
Contact loading 50 V DC / 0.5 A
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Mechanical life 107 switching cycles