Switching function Normally closed (NC)
Output type NAMUR with safety function
Rated operating distance 5 mm
Installation flush
Assured operating distance 0 ... 4.05 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Safety Integrity Level (SIL) up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation.
Output type 2-wire
Nominal ratings
Nominal voltage 8.2 V (Ri approx. 1 kΩ)
Switching frequency 0 ... 500 Hz
Current consumption
Measuring plate not detected ≥ 3 mA
Measuring plate detected ≤ 1 mA